RO & Evaporator Scale Control: The Guide to Better Performance

Jun 27th 2018

Scale is a crust that forms on membranes, heat transfer surfaces, and on the inside of pipes as salts precipitate out of solution. Scale blocks flow, disrupts heat transfer, and increases energy requirements for water treatment systems. Simply stated, scale is bad news: it limits system performance and increases maintenance costs.

 

You can protect your plant’s productivity from scale when you are armed with an understanding of scaling water chemistry and the right technology. You can also push and maximize performance of your plant, if you understand the scaling ‘danger zone’.

 

Download our periodic table, which includes an easy-to-use guide and example. Keep reading below to learn more. 

Periodic table of scaling compounds
Periodic table of scaling compounds

How do Scaling Ions Precipitate?

Scaling occurs when ion pairs reach their solubility limits and form salts. Ion pairs comprise positive cations and negative anions, and most scale is caused by ions that are multivalent pairs. Multivalent ions, such as calcium (Ca2+) and sulfate (SO42-), are more likely to cause scale than monovalent ions because they have lower solubilities and will precipitate earlier. Watch out, however, for one particular mono-multi pair—calcium (Ca2+) and fluoride (F)—which can also cause scale.

 

Our chemists and engineers use the above periodic table of scaling compounds to easily check for concentrations of ions in water that might precipitate and affect evaporator or membrane system performance.

 

The solubility of an individual ion pair is the most essential information to use when designing a scale management strategy. However, scaling concentration limits can be affected by the temperature, pH, and mixed-ion chemistry of the water. Ions in mixed solutions tend to have higher solubilities than pure solutions, which can be difficult to predict, even with some of the software models that are available. We treat mixed-ion effects as an extra buffer that prevents scale.

Photo of scaling found on the interior surface of pipes
Scaling found on the inside of pipes

How Does Scaling Impact Evaporators & Membrane Systems?

Any heat transfer surface where scaling occurs will observe decreased efficiency and capacity. Although scaling is typically shown on metal surfaces, it can also form on membranes used in reverse osmosis systems and reduce membrane performance. In severe cases, scale can mechanically damage or rupture the membrane.

 

A plant that ignores scaling limits can experience equipment plugging and surface crusting, or be operating sub-optimally for leaving room to increase freshwater recovery. Time and money are wasted on either low performance or efforts to recover from a scaling event. Although carbonate scaling is easy to remove with acid, other scales take much more effort, such as using expensive chemical cleans or mechanical removal. It is best to know your water chemistry so that you can prevent scaling, rather than try to deal with it after it forms.

How to Avoid Scaling in Your Industrial Water Treatment Process

Follow these basic guidelines to help prevent scale build-up that leads to decreased performance and increased costs.

 

  • Get a complete analysis of your water chemistry to understand the concentrations of your potential scaling ions. For a few hundred dollars, you will receive analytical data that will help you understand your water. Ensure you sample during periods of both low and high concentration for a better representation of your water chemistry.
  • Know the scaling potential of any scaling ions in your water by using our Periodic Table of Scaling Compounds, or find a software package if you wish to be more advanced.
  • Design and operate your process to push recovery, but avoid exceeding solubility limits of scaling ions.
  • Consider automated chemical softening that uses precision dosing to minimize the risk of scale formation, while also reducing wasted chemicals that may result from manual chemical softening.
  • Consider adding anti-scalants that may boost your scaling ion solubilities as much as 3–4x, but be sure to use the correct anti-scalant and consider testing. Many companies will sell you anti-scalants and their performance may vary.

Contact an expert at Saltworks today to optimize your process and prevent scale formation.

About Saltworks

Saltworks Technologies is a leader in the development and delivery of solutions for industrial wastewater treatment and lithium refining. By working with customers to understand their unique challenges and focusing on continuous innovation, Saltworks’ solutions provide best-in-class performance and reliability. From its headquarters in Richmond, BC, Canada, Saltworks’ team designs, builds, and operates full-scale plants, and offers comprehensive onsite and offsite testing services with its fleet of mobile pilots.

Related Resources

Photo of a ScaleSense real-time sensor/analyzer for scaling ions
Article

Real-Time Sensing and Process Control: Introducing ScaleSense

Real-time measurement provides prompt feedback for controls. A real-time sensor can help to optimize your process, reduce risk, and minimize operational and maintenance demand. Saltworks has developed a new real-time sensor—that is simple and robust—to operate in the high-TDS range.

A photo of a wastewater disposal truck used in brine management
Article

How to Manage Brine Disposal & Treatment

The many options for managing brine, a term for saline wastewater from industrial processes, fall under two categories: brine treatment and brine disposal. Brine treatment involves desalinating the brine for reuse and producing a concentrated brine (lower liquid waste volume), or residual solids (zero liquid discharge).